Skip to content

Commercial kitchens

Gas interlocks in commercial kitchens: do you need one, and what do the rules say?

A gas interlock links a commercial kitchen's mechanical ventilation to its gas supply, so the gas shuts off if the extraction fails. GSIUR regulation 27(4) is the legal root and HSE says installers should fit one, but BS 6173:2020 isn't retrospective: an older kitchen without one needs a risk assessment. Book a CP42 online or call us.

By the London Gas Cert team Updated How we write and check our pages

6 min read

Price confirmed on booking

Get a price 020 8058 4241

A gas interlock connects a commercial kitchen's mechanical ventilation to its gas supply. If the extraction stops, or was never switched on, the interlock shuts off the gas to the cooking appliances. HSE says installers should fit one wherever mechanical ventilation serves gas appliances, and the legal root is regulation 27(4) of the Gas Safety (Installation and Use) Regulations 1998. Existing kitchens without one are judged on risk.

What is a gas interlock?

A control system that stops the gas flowing to your cooking appliances unless the kitchen's mechanical ventilation is working. It watches the extraction (and, where fitted, the supply fans) and, if they fail, it shuts off the gas to the appliances. HSE's catering guidance also says manual bypasses to interlock systems are not permitted.

The reason is simple. Cooking produces combustion products and heat, and the ventilation keeps both within safe limits. HSE's guidance warns that if a mechanical system fails or isn't working correctly, the kitchen environment may become unsafe or unfit for work. An interlock turns that risk into an automatic stop.

How it works in practice

Sensors prove the fans are running, usually by monitoring the fan motor current or the air pressure in the system, and an automatic valve on the kitchen's gas supply opens only while they do. Industry practice is to interlock both the extract and the supply fans where both are fitted. When the gas has been cut, it stays off at least until the ventilation is running again.

Where the rules come from

  • The law: GSIUR regulation 27(4) says no one may install a power-operated flue system for a gas appliance unless it safely prevents the appliance operating if the draught fails. Regulation 35 then requires the whole installation to be kept safe.
  • HSE guidance: CAIS23, Gas safety in catering and hospitality, and CAIS10, Ventilation in catering kitchens.
  • Standards: BS 6173:2020 for installing and maintaining gas catering appliances, and IGEM/UP/19 Edition 2 for the design and application of interlock devices in catering, with a supplement for engineers.

Does my kitchen need a gas interlock?

A new installation with mechanical ventilation should have one. For an existing kitchen without one, the answer depends on risk: BS 6173 isn't retrospective, so the lack of an interlock isn't automatically unlawful, but HSE says to assess whether a risk is likely to arise and, if so, make sure it is prevented or controlled.

Your kitchenWhat appliesWhat to expect
New kitchen, or a new gas catering installationGSIUR reg 27(4); HSE: the installer should fit an interlock; BS 6173:2020An interlock between the mechanical ventilation and the gas supply, with no manual bypass
Existing kitchen with an interlockGSIUR reg 35: keep it in a safe conditionThe interlock is checked at each catering inspection and kept working
Existing kitchen without an interlockGSIUR reg 35; HSE CAIS23 risk assessment; BS 6173 is not retrospectiveA risk assessment; if factors increase the risk, an AR or ID classification may be applied

What "not retrospective" means

HSE's guidance says British Standards are not a statement of the law but set out agreed good practice, and that BS 6173 is not retrospective. An older kitchen doesn't have to be rebuilt to today's standard just because the standard changed. It does have to be safe, and the risk assessment is how you show that.

Changing appliances or ventilation

If you are adding or replacing appliances, changing the canopy or altering the fans, ask your engineer before the work whether it changes what your kitchen needs. Don't assume an existing arrangement carries over.

How is a kitchen without an interlock assessed?

By weighing the factors that make a build-up of fumes more or less likely. HSE's CAIS23 lists both. If the engineer finds factors that increase the risk, an At Risk or Immediately Dangerous classification may be applied, depending on the nature and level of the risk. Fitting an interlock is one of the factors HSE lists as reducing it.

Factors that increase the risk (HSE CAIS23):

  • evidence that the ventilation isn't used or is unreliable;
  • a small kitchen;
  • obviously poor design or maintenance of the ventilation, such as long, convoluted ducts, broken fans, leaking ductwork or cooking fumes and steam visibly escaping;
  • staff who don't understand the effect of using gas appliances without adequate ventilation;
  • poor general ventilation;
  • long periods of heavy gas use without the ventilation working properly;
  • an ageing system or installation;
  • no routine or planned maintenance.

Factors that reduce the risk:

  • good natural ventilation, or satisfactory fume removal through the ductwork by natural draught alone;
  • a well-maintained, modern ventilation system;
  • an appropriate ventilation interlock;
  • staff who understand the risks, with documented procedures for using the ventilation;
  • minimal use of gas appliances, or a large room;
  • clear, permanent notices warning that appliances must not be used without the ventilation running.

If you have concerns about your kitchen, HSE's advice is not to wait for the next routine visit: get urgent advice from a competent gas engineer and, where necessary, a ventilation expert.

Is there a CO₂ level that fails a kitchen?

Not one set in law or in HSE's catering guidance. Neither GSIUR nor CAIS23 gives a carbon dioxide figure that makes a kitchen pass or fail. What HSE's guidance does set out is how a carbon monoxide or carbon dioxide alarm system should behave where one is fitted, and that it is a back-up, not a replacement for ventilation.

According to CAIS23, such a system should:

  1. give an audible alarm;
  2. be interlocked to the gas supply with an automatic gas shut-off;
  3. be fail-safe;
  4. need someone to restore the gas supply by hand.

HSE also stresses that these alarms are only warning devices. The primary safeguards remain an adequate and effective ventilation system, and regular maintenance and servicing of all equipment by competent people. Domestic CO alarms are not normally suitable for commercial kitchens and should not be used. If your kitchen has a monitoring system, ask your engineer to explain how it is set up and tested.

What does the engineer check at a CP42 inspection?

Part 1 of the CP42 form covers the kitchen environment: isolation, interlocks, extraction and ventilation. In practice the engineer checks that the interlock does its job (that the gas to the appliances shuts off when the ventilation fails) and looks for any bypass, then inspects each appliance in Part 2.

Everything the engineer finds goes on the record, including any Immediately Dangerous or At Risk classification and what was done about it.

Keeping the interlock reliable

HSE notes that effective preventative maintenance and cleaning help prevent nuisance shutdowns caused by the ventilation failing. Keep the fans, filters and ductwork on a maintenance schedule, and keep the records. Duct cleaning is a fire-safety matter next to, not part of, the gas certificate, but a well-maintained system also helps keep the interlock from tripping.

Can an interlock be bypassed or switched off?

No. HSE's catering guidance says the installation of manual bypasses to interlock systems is not permitted. A bypass defeats the automatic protection the interlock gives you if the ventilation fails. If staff have been bypassing the interlock because of nuisance trips, fix the cause and remove the bypass.

Our guide to what happens when a gas safety check fails explains the ID and AR classifications, and what environmental health officers check covers how an inspector is likely to view your kitchen's gas arrangements.

Who designs and fits an interlock?

A Gas Safe registered engineer with commercial catering categories, often working with a ventilation specialist. Fitting or upgrading an interlock is installation work, separate from the CP42 inspection that checks it. HSE's guidance points to a competent gas engineer and, where necessary, a ventilation expert.

If you're not sure whether your kitchen, or part of a building, needs a CP42 or a different record, see CP12 vs CP17 vs CP42.

Key points

  • A gas interlock shuts off the gas to the cooking appliances if the kitchen's mechanical ventilation fails.
  • The legal root is GSIUR regulation 27(4); HSE says installers should interlock mechanical ventilation with the gas supply, and manual bypasses are not permitted.
  • BS 6173:2020 is good practice, not law, and isn't retrospective: an existing kitchen without an interlock needs a risk assessment and may be classified AR or ID.
  • Neither the law nor HSE's catering guidance sets a CO₂ pass mark; CO and CO₂ alarm systems are back-ups to ventilation, and domestic CO alarms aren't suitable.
  • Part 1 of the CP42 inspection covers isolation, interlocks, extraction and ventilation.

Book a catering gas safety inspection

Book a catering gas safety certificate (CP42) and tell us about your ventilation and whether the kitchen has an interlock. Price: Price confirmed on booking; see our prices. Book online or call 020 8058 4241.

Illustration of a catering gas safety check: a range, a fryer and a chargrill under the extract canopy, with the extract fan and supply air, the gas interlock panel, the isolation valve and the emergency button. FANS GAS SAFE TO USE
What a catering gas safety check (CP42) covers: the range, fryer and chargrill under the extract canopy, the gas interlock, the isolation valve and the emergency button.
The four results of a gas safety check, most serious first: Immediately Dangerous (disconnected), At Risk (turned off), advice (noted) and safe to use. ID Disconnected AR Turned off Advice Noted Safe Safe to use
How an engineer classifies what they find, under the gas industry unsafe situations procedure (IGEM/G/11 Edition 2).
Sources for this page

Facts checked . General information, not legal advice.

Quick answers

Questions

Is a gas interlock a legal requirement in a commercial kitchen?
For a new installation, expect to need one: GSIUR regulation 27(4) bars installing a power-operated flue system that doesn't safely stop the appliance if the draught fails, and HSE says installers should interlock mechanical ventilation with the gas supply. BS 6173:2020 isn't retrospective, so an existing kitchen without one isn't automatically unlawful, but the risk must be assessed and may lead to an AR or ID classification.
What happens if the extraction fan stops?
With a working interlock, the gas supply to the cooking appliances shuts off automatically and stays off at least until the ventilation is running again. That is the point of the system: cooking produces combustion products and heat that the ventilation has to remove. Regular maintenance and cleaning of the ventilation, HSE notes, help prevent nuisance shutdowns.
Can we bypass the interlock if it keeps tripping?
No. HSE's catering guidance says the installation of manual bypasses to interlock systems is not permitted. If the interlock trips often, the cause is usually in the ventilation system or its maintenance, so have the fans, filters and sensors checked by a competent engineer. Keep a record of the fault and the repair.
Do I need a carbon monoxide alarm in a commercial kitchen?
HSE's guidance asks you to consider CO alarms or monitoring in your kitchen risk assessment rather than requiring them. If you fit one, it must suit commercial conditions: domestic CO alarms are not normally suitable and should not be used. A fitted alarm system should sound an alarm, shut off the gas automatically, fail safe, and need someone to restore the gas by hand.

Book your gas safety check

Landlord, commercial or catering: choose your certificate, check the price and pick a preferred date — or call the office.

Call us Get a price