Commercial kitchens
Does a domestic cooker in a café need a catering gas safety check (CP42)?
Usually, yes. A domestic cooker used to cook for customers is gas equipment at a place of work, so GSIUR regulation 35 requires it to be kept safe, and it's generally inspected as commercial catering equipment by an engineer with the commercial catering category. There's no fixed legal interval; HSE says annual inspection is a reasonable minimum. Book online.
By the London Gas Cert team Updated How we write and check our pages
7 min read
Usually, yes. Once a domestic cooker is used to cook food for customers, it's gas equipment at a place of work, and the business must keep it safe under regulation 35 of the Gas Safety (Installation and Use) Regulations 1998 (GSIUR). In practice it's inspected as catering equipment, recorded on a CP42, by an engineer who holds the commercial catering category. What the kitchen needs beyond that depends on how the cooker is used, what's around it and how the kitchen is ventilated.
Why is a domestic cooker in a café treated as commercial catering?
Because the law looks at where the cooker is used, not what it was built for. Regulation 35 requires every employer and self-employed person to keep any gas appliance, installation pipework or flue at a place of work under their control in a safe condition. A café kitchen is a place of work, so the domestic cooker in it comes under the same duty as a commercial range.
The industry standards point the same way. BS 6173:2020, the British Standard for installing and maintaining gas catering appliances, covers domestic cookers used commercially. Gas Safe Register's technical bulletin on work categories, TB014, says that where a domestic cooker is installed in non-domestic premises alongside other catering appliances, it falls within the scope of BS 6173, and the engineer needs a relevant commercial catering work category.
A cooker on its own
A single domestic cooker in a small café is judged on its setting. TB014 asks whether the appliance is installed in the kind of environment it was designed for, whether the manufacturer's installation instructions allow it there, and whether it stands alone or forms part of an installation with other catering appliances. A cooker used every day to cook for paying customers is working in a commercial setting, which is why these cookers are generally treated as catering equipment.
TB014 also notes that a concession to the manufacturer's instructions may be needed to confirm that a domestic appliance is suitable for a non-domestic environment, where the manufacturer's literature doesn't say so. An engineer installing an appliance somewhere it wasn't designed for has to seek the manufacturer's guidance. Check your cooker's instructions, and give your engineer the make and model when you book.
The law, the guidance and the standards
- The law: GSIUR regulation 35, alongside the Health and Safety at Work etc Act 1974.
- HSE guidance: CAIS23, Gas safety in catering and hospitality, which sets out what HSE expects of catering businesses using gas.
- Standards: BS 6173:2020, which HSE describes as agreed good practice rather than a statement of the law, and which isn't retrospective.
Which record do you need?
Choose by how the cooker is used and where it sits. The table covers the common cases.
| Setting | Record | Engineer's category |
|---|---|---|
| A café or takeaway cooking for customers on a domestic cooker | Catering inspection (CP42) | Commercial catering |
| A commercial kitchen with a domestic cooker alongside commercial ranges or fryers | Catering inspection (CP42); TB014 places the cooker within BS 6173 | Commercial catering |
| A school food technology room with several domestic cookers | TB014 says IGEM/UP/11 guidance treats this as a non-domestic catering installation, to BS 6173 and interlocked under IGEM/UP/19 | Commercial catering |
| A let flat above the café with its own cooker | Landlord gas safety record (CP12), under regulation 36 | Domestic |
| A cooker staff use to heat their own meals | Still gas equipment at a place of work under regulation 35; tell us how it's used when you book | Depends on the setting |
B&Bs and guest houses
A B&B that cooks guests' breakfasts in the owner's own kitchen is a different case. IGEM's guidance for engineers in catering establishments notes that BS 6173, as currently written, isn't intended to apply to dwellings or primarily domestic premises such as bed and breakfast installations. The guest rooms, meanwhile, fall under the landlord rules: HSE names B&Bs among those who need a landlord gas safety check. Our guide to gas safety for holiday lets, B&Bs and lodgers covers that side.
Who can inspect a domestic cooker in a commercial kitchen?
A Gas Safe registered business, with an engineer who holds the commercial catering category. Gas work may only be done by, or by an employee of, a Gas Safe registered business (GSIUR reg 3(3)). Gas Safe Register's commercial ID card categories include Commercial Catering, which covers installing, commissioning, disconnecting, servicing and repairing commercial gas catering appliances.
A domestic cooker category on its own isn't enough where TB014 places the cooker within BS 6173. HSE's guidance says the back of the engineer's Gas Safe ID card shows the areas of gas work they're competent in, so ask to see it before the work starts.
What does the engineer check?
The kitchen first, then each appliance, as with any CP42. Part 1 covers the kitchen environment: gas isolation, any interlock, extraction and ventilation. Part 2 covers each gas catering appliance, the domestic cooker included.
HSE's catering guidance sets out what engineers look for, and several points matter for domestic cookers:
- Flame supervision devices, which stop gas reaching a burner if its flame goes out. New equipment has them; second-hand equipment with open or enclosed burners should be fitted with them when it's installed; and ovens without one should already have been upgraded or, where that isn't possible, replaced.
- Connections and restraints. Restraints are checked, and flexible gas connectors can be damaged when equipment is moved.
- Staff training. Everyone who uses the gas equipment should be trained to use it and to make visual checks for obvious faults, such as damaged pipework and connections or a smell of gas.
Ventilation and interlocks
Where a kitchen has mechanical ventilation, HSE's guidance says the installer should fit an interlock, so that if the ventilation fails, the gas supply to the appliances shuts off; manual bypasses aren't permitted. BS 6173 isn't retrospective, so an existing kitchen without an interlock doesn't automatically fail. The risk has to be assessed instead, and if the engineer finds factors that increase it, an At Risk or Immediately Dangerous classification may be applied.
If you're about to add or replace a cooker, or change the extraction, ask your engineer before the work whether it changes what the kitchen needs. Our guide to commercial kitchen gas interlocksexplains how kitchens without one are assessed.
Carbon monoxide alarms
A domestic CO alarm isn't the answer in a café kitchen. HSE's catering guidance says domestic CO alarms are not normally suitable for commercial kitchens and should not be used. Where a CO or CO₂ alarm system is fitted, it should give an audible alarm, be interlocked to shut off the gas automatically, fail safe and need someone to restore the gas supply by hand.
How often should it be inspected?
There's no fixed legal interval for a catering inspection. HSE says annual inspection is a reasonable minimum, and renewing the CP42 every 12 months is industry standard. Insurers and environmental health officers usually expect to see a current record, and council officers often ask for gas records during food hygiene inspections. Our guide to what environmental health officers check explains what they look for.
Moving the cooker, adding appliances or changing the ventilation are good reasons for a check in between.
Key points
- A domestic cooker used to cook for customers is gas equipment at a place of work, covered by GSIUR regulation 35.
- It's generally inspected as catering equipment on a CP42, by an engineer with the commercial catering category; TB014 places a domestic cooker installed alongside other catering appliances within BS 6173.
- Check that the manufacturer's instructions allow commercial use; a concession to those instructions may be needed.
- Where a kitchen has mechanical ventilation, HSE expects an interlock; existing kitchens without one need a risk assessment, because BS 6173 isn't retrospective.
- Domestic CO alarms aren't suitable for commercial kitchens.
- There's no fixed legal interval; HSE says annual inspection is a reasonable minimum.
Book a catering gas safety inspection
Book a catering gas safety certificate (CP42) online, and tell us the cooker's make and model, the other gas appliances in the kitchen and how the kitchen is ventilated. Price: Price confirmed on booking; see our prices. Book online or call 020 8058 4241. If part of the building is let as a home, see CP12 vs CP17 vs CP42 for which records you need.
Sources for this page
Facts checked . General information, not legal advice.
- legislation.gov.uk: https://www.legislation.gov.uk/uksi/1998/2451/regulation/35
- legislation.gov.uk: https://www.legislation.gov.uk/uksi/1998/2451/regulation/3
- legislation.gov.uk: https://www.legislation.gov.uk/uksi/1998/2451/regulation/36
- HSE: https://www.hse.gov.uk/pubns/cais23.htm
- HSE: https://www.hse.gov.uk/pubns/cais23.pdf
- registeredgasengineer.co.uk: https://registeredgasengineer.co.uk/technical/technical-bulletin-014-b-working-within-scope-of-work-categories/
- thenbs.com: https://www.thenbs.com/PublicationIndex/DocumentSummary.aspx?DocID=328784
- IGEM: https://www.igem.org.uk/resource/igem-up-19-edition-2-supplement-1-guidance-for-gas-engineers-to-the-application-of-relevant-sections-of-igem-up-19-in-catering-establishments.html
- IGEM: https://www.igem.org.uk/resource/igem-up-11-edition-3-gas-installations-for-educational-establishments.html
- Gas Safe Register: https://www.gassaferegister.co.uk/media/1826/defining-the-commercial-id-card-work-categories.pdf
- CORGIdirect: https://www.corgi-direct.com/gas-safety-inspection-form-17950-3421023
- HSE: https://www.hse.gov.uk/gas/landlords/safetycheckswho.htm
- HSE: https://www.hse.gov.uk/gas/domestic/faqlandlord.htm
- legislation.gov.uk: https://www.legislation.gov.uk/uksi/1998/494/contents